SiBE061121.book Page 120 Monday, April 25, 2011 3:21 PM
Check
5.2

Fan Motor Connector Check

Check No.02
1. Check the connection of connector.
2. Check the motor power supply voltage output (pins 4 - 7).
3. Check the motor control voltage (pins 4 - 3).
4. Check the rotation command voltage (pins 4 - 2).
5. Check the rotation pulse (pins 4 - 1).
5.3

Power Supply Waveforms Check

Check No.11
Measure the power supply waveform between No. 1 and No. 2 on the terminal board, and check
the waveform disturbance.
Fig.1
120
S1
7
6
5
4
3
2
1
Check to see if the power supply waveform is a sine wave. (Fig.1)
Check to see if there is waveform disturbance near the zero cross. (sections circled in Fig.2)
Motor power supply voltage (310 ~ 340 VDC)
Unused
Unused
GND
Motor control voltage (15 VDC)
Rotation command voltage (1 ~ 6 VDC)
Rotation pulse
(R12099)
Fig.2
SiBE061121
Service Diagnosis