12.3
Description
Gas category 2H: G20
Diameter of the venturi
restrictor
Nominal Load (gross)
Nominal output
Supply pressure
CO
(full load)
2
O
(full load)
2
Gas consumption
(1)
NO
-emission
x
Mass flow rate flue gases
(minimal load)
Mass flow rate flue gases
(nominal load)
Flue gas temperature
(nominal load)
Gas category 3P: G31
Diameter of the venturi
restrictor
Nominal Load (gross)
Nominal output
Supply pressure
Gas control valve pressure
CO
(full load)
2
O
(full load)
2
Gas consumption
NO
-emission
x
Mass flow rate flue gases
(minimal load)
Mass flow rate flue gases
(nominal load)
Flue gas temperature
(nominal load)
1 - Based on 1013.25 mbar and 15°C.
0311753_SGS_28-120_II_UKUK_V2.0 , 2017-05-03

Gas details

Unit
SGS 28
mm
-
kW
32.2
kW
31.0
mbar
20
vol%
9.0 ± 1.0
vol%
4.8 ± 1.8
3
3.1
m
/h
mg/kWh GCV
24
kg/h
24.3
kg/h
52.2
ºC
44
mm
6.00
kW
31.5
kW
31.0
mbar
37 / 50
mbar
12.0 ± 2.0
vol%
10.0 ± 1.0
vol%
5.7 ± 1.8
kh/h
2.3
mg/kWh GCV
31
kg/h
24.8
kg/h
53.3
ºC
44
SGS 30
SGS 50
-
-
33.3
52.2
32.7
50.3
20
20
9.0 ± 1.0
9.0 ± 1.0
4.8 ± 1.8
4.8 ± 1.8
3.2
5.0
32
36
24.3
24.3
54.0
84.6
54
63
6.00
6.00
32.6
51.1
32.7
50.3
37 / 50
37 / 50
12.0 ± 2.0
12.0 ± 2.0
10.0 ± 1.0
10.0 ± 1.0
5.7 ± 1.8
5.7 ± 1.8
2.3
3.7
39
42
24.8
24.8
55.2
86.4
54
63
SGS 60
-
63.3
60.4
20
9.0 ± 1.0
4.8 ± 1.8
6.0
37
24.3
102.6
68
6.00
62.0
60.4
37 / 50
12.0 ± 2.0
10.0 ± 1.0
5.7 ± 1.8
4.4
45
24.8
104.8
68
113