VISTA-128BPT/128BPT-SIA/250BPT INSTALLATION AND SETUP GUIDE
Installing V-PLEX
The polling loop provides both power and data to the V-PLEX devices, and is constantly monitoring the status of all
zones enabled on the loop. The maximum current draw of all devices on the polling loop cannot total more than 128mA
(unless the system uses a 4297 Polling Loop Extender Module).
Devices that can be programmed via either DIP switches or the built-in unique serial number must be set for
the serial number mode operation.
All devices on the polling loop must be wired in parallel to the [+] and [-] polling loop terminals of the control panel (24
and 25). You can wire from device to device, or have multiple branches connected directly to the control panel in a star
configuration.

Compatible Polling Loop Devices

Door/Window Contacts
4190SN
Serialized 2-Zone Expander
4193SN
Serialized 2-Zone Expander
4193SNP
Serialized 1-Zone Expander
4208SN
8 Zone V-PLEX Interface
4208SNF
8 Zone V-PLEX Class A Interface
4208U
Universal 8-Zone Expander
4939SN
Surface Mount Contact
Aluminum Overhead Door
4959SN
Contact
Interior Motion Detection
DT7500SN
V-PLEX Dual Tech PIR
IS2500SN
V-PLEX/SIM Dual Tech
Interior Glass Break Detection
FG1625SN
Glass Break Detector
UL
The 4297 must be powered from the control panel's Auxiliary Power Output or from a UL Listed
supplementary power supply.
For new polling loop installations, always use twisted pair wiring. In many cases, existing non-twisted pair
wiring may be used, but it is more susceptible to interference from other sources, and may be problematic
in installations with long wire runs or in high noise environments.
Always locate polling loop wiring at least 6 inches (15cm) of AC power, telephone, or intercom wiring. The
polling loop carries data between the control panel and the devices; interference on this loop can cause
an interruption of communication. The polling loop can also cause outgoing interference on the
intercom or phone lines. If this spacing cannot be achieved, shielded wire must be used. (Note that the
maximum total wire length supported is cut in half when shielded wire is used.)
No more than 64mA may be drawn on any individual wire run.
®
Devices
Hold Up Devices
269SN
V-PLEX Holdup Switch
Fire Devices
5193SD
Photoelectric Smoke Detector Device
Photoelectric Smoke Detector w/Heat
5193SDT
Detector
4209U
4 zone, 2-Wire Smoke Expansion Module
Output Devices
4101SN
Serial Number Single-Output Relay Module
Extenders/Isolators
VPLEX-VSI
V-PLEX Short Isolator
4297
Extender Module
4-26