DN
Item
High-ceiling adjustment
(Air flow selection)
5d
Built-in filter
Static pressure selection Concealed duct standard
Timer setting
60
(wired remote controller)

1-way air discharge cassette (SH)

Value
Type
0000
Standard (factory default)
0001
High-ceiling (1)
0003
High-ceiling (3)

2-way air discharge cassette

Value
Type
0000
Standard (factory default)
0001
High-ceiling (1)
0003
High-ceiling (3)
* The high-ceiling installation of model AP007 to AP012 can only be
undertaken when the combined capacity of the indoor units connected is
100% or less than the capacity of the outdoor unit.
Do not proceed with high-ceiling installation if this limit is exceeded.

4-way air discharge cassette

Type
Value
Air flow at outlet
4 directions 3 directions 2 directions 4 directions 3 directions 2 directions
Standard
0000
2.7 m
(factory default)
0001
High-ceiling (1)
0003
High-ceiling (3)
Type
Value
Air flow at outlet
4 directions 3 directions 2 directions 4 directions 3 directions 2 directions
Standard
0000
3.0 m
(factory default)
0001
High-ceiling (1)
3.3 m
0003
High-ceiling (3)
3.6 m
Under ceiling
Value
Type
0000
Standard (factory default)
0001
High-ceiling (1)
2-way air discharge cassette
0000: Standard filter (factory default)
0001: Super long-life filter
4-way air discharge cassette
0000: Standard filter (factory default)
Under ceiling
0000: Standard filter (factory default)
Concealed duct standard
0000: Standard filter (factory default)
0001: High-performance filter (65%, 90%)
0000: Standard (factory default)
0001: High static pressure 1
0003: High static pressure 2
0006: Low static pressure
0000: Available (can be performed)
Description
AP015, AP018
3.5 m or less
4.0 m or less
4.2 m or less
AP007~AP030
2.7 m or less
3.2 m or less (*)
3.8 m or less (*)
AP009~AP012
2.8 m
3.0 m
2.8 m
3.2 m
3.5 m
AP024~AP030
3.3 m
3.6 m
3.0 m
3.5 m
3.8 m
3.3 m
3.8 m
3.6 m
AP015~AP056
3.5 m or less
4.0 m or less
Slim Duct
0000: Standard (factory default)
0001: High static pressure 1
0003: High static pressure 2
0006: High static pressure 3
0001: Unavailable (cannot be
performed)
− 87 −
0000: Standard
AP024
3.8 m or less
4.0 m or less
4.2 m or less
AP036~AP056
2.7 m or less
3.0 m or less
3.5 m or less
AP015~AP018
3.2 m
3.5 m
3.5 m
3.8 m
3.8 m
AP036~AP056
3.3 m
3.6 m
3.5 m
3.8 m
3.8 m
0000: Available