8-4. Check Codes Displayed on Remote Controller and
SMMS-e Outdoor Unit (7-Segment Display on I/F
Board) and Locations to Be Checked
For other types of outdoor units, refer to their own service manuals.
Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
E01
E02
E03
E04
No. of indoor units from
which signal is received
normally
E06
E06
E07
Location
of
Description
System status
detection
Remote
Indoor-remote
Stop of
controller
controller
corresponding
communication
unit
error
(detected at
remote
controller end)
Remote
Remote
Stop of
controller
controller
corresponding
transmission
unit
error
Indoor
Indoor-remote
Stop of
unit
controller
corresponding
communication
unit
error
(detected at
indoor end)
Indoor
Indoor-outdoor
Stop of
unit
communication
corresponding
circuit error
unit
(detected at
indoor end)
Signal lack of
I/F
All stop
indoor unit
I/F
Indoor-outdoor
All stop
communication
circuit error
(detected at
outdoor end)
− 172−
Error detection
Check items (locations)
condition(s)
Communication between
• Check remote controller
indoor P.C. board and remote
inter-unit tie cable (A/B).
controller is disrupted.
• Check for broken wire or
connector bad contact.
• Check indoor power
supply.
• Check for defect in indoor
P.C. board.
• Check remote controller
address settings
(when two remote
controllers are in use).
• Check remote controller
P.C. board.
Signal cannot be transmitted
• Check internal
from remote controller to
transmission circuit of
indoor unit.
remote controller.
--- Replace remote
controller as necessary.
There is no communication
• Check remote controller
from remote controller
and network adaptor
(including wireless) or
wiring.
network adaptor.
Indoor unit is not receiving
• Check order in which
signal from outdoor unit.
power was turned on for
indoor and outdoor units.
• Check indoor address
setting.
• Check indoor-outdoor tie
cable.
• Check outdoor terminator
resistor setting (SW30,
Bit 2).
Indoor unit initially
• Check power supply to
communicating normally fails
indoor unit.
to return signal for specified
(Is power turned on?)
length of time.
• Check connection of
indoor-outdoor
communication cable.
• Check connection of
communication connectors
on indoor P.C. board.
• Check connection of
communication connectors
on outdoor P.C. board.
• Check for defect in indoor
P.C. board.
• Check for defect in outdoor
P.C. board (I/F).
• Check outdoor terminator
Signal cannot be transmitted
resistor setting (SW30,
from outdoor to indoor units
for 30 seconds continuously.
Bit 2).
• Check connection of
indoor-outdoor
communication circuit.