Bumpless Operation - Toshiba Tosvert VF-S15 Instruction Manual

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

6.16 Bumpless operation

f295 : Bumpless operation selection
f732 : Local/remote key prohibition of extension panel
f750 : Easy key function selection
 Function
[Parameter setting]
Title
f295
f732
6
 EASY key function selection
● Set Local/remote function to
f750 (EASY key function selection) = 2 (Local / remote key).
EASY lamp is lighting during local mode.
● Local mode is the operation using operation panel.
Remote mode is the operation method selected by the command mode selection: cmod and Frequency
setting mode selection: fmod
● LOC/REM key of extension panel option (RKP007Z) is available.
In this case, set parameter f732 (Local/remote key prohibition of extension panel) = 0 (Permitted).
When switching from Remote mode to Local mode, the status of start and stop, and operating
frequency at Remote mode are moved to Local mode.
Running status of Local mode will not moved to Remote mode when switching from Local mode to
Remote mode.
Function
Bumpless operation selection
Local/remote key prohibition of
extension panel
EASY
Adjustment range
0: Disabled
1: Enabled
0: Permitted
1: Prohibited
0: Easy / standard setting mode
switching function
1: Shortcut key
2: Local / remote key
3: Monitor peak / minimum hold
trigger
4: -
5: -
key.
F-54
E6582175
Default setting
0
1
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents