Omron CJ1W-CT021 Operation Manual page 130

High-speed counter units
Hide thumbs Also See for CJ1W-CT021:
Table of Contents

Advertisement

Memory Allocation
Word
m+75
00-15
m+76
00-03
04-15
m+77
00-03
04-07
08-15
m+78, m+79
00-15
m+80, m+81
00-15
m+82, m+83
00-15
m+84
00-15
m+85, m+86
00-15
m+87, m+88
00-15
m+89, m+90
00-15
m+91, m+92
00-15
110
Bit
Item
Counter Type
Signal Type
---
Z-reset Mode
Overflow/Underflow
error-code generation
---
Upper Count Limit
Circular/Linear
Lower Count Limit
Linear
Initial Count Value
Time-window
(Rate Measurement)
Rate-Range 0
Lower Limit
Rate-Range 0
Upper Limit
Set Pattern
Rate-Range 0
Reset Pattern
Rate-Range 0
Counter 2
Counter Type:
0 = Circular (=default)
1 = Linear
Signal Type:
0 = Phase Differential (x1) (=default)
1 = Phase Differential (x2)
2 = Phase Differential (x4)
4 = Up & Down Pulse
8 = Pulse & Direction
Not used
Functionality of Z input signal:
0 = No function (=default, only mapped in CIO)
1 = Reset (Counter at rising edge)
Generate error-code at Overflow/Underflow:
0 = No error-code generation (only report with Overflow/
Underflow-bits and outputs keep last state)
1 = Error-code generation (report error-code and turn
OFF all outputs)
Not used
Circular/Linear Counter: Upper Count Limit
Linear Counter: Lower Count Limit
Initial Counter Value after transfer of Unit configuration
data
Set time-window Counter 2 between 1 and 9999
to configure Rate Measurement (0 means that NO rate
measurement is required)
Rate-Range 0 Lower Limit
Rate-Range 0 Upper Limit
Output Set Pattern Rate-Range 0
Output Reset Pattern Rate-Range 0
Section 4-2
Function
ms
(BCD)