Appendix 1.3 List Of Error Codes (1000 To 1999) - Mitsubishi Electric Q26UD(E)HCPU User Manual

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Appendix 1.3
The following table shows the error messages, the error contents and causes, and the corrective actions for the error
codes (1000 to 1999).
Error
Error and cause
code
[MAIN CPU DOWN]
Runaway or failure of the CPU module
• Malfunction due to noise or other causes
• Hardware failure
■Collateral information
• Common information: -
• Individual information: Failure information
(QnUDVCPU only)
■Diagnostic timing
• Always
1000
[CPU UNIT DOWN]
Runaway or failure of the CPU module
• Malfunction due to noise or other causes
• Hardware failure
■Collateral information
• Common information: -
• Individual information: Failure information
■Diagnostic timing
• Always
[MAIN CPU DOWN]
Runaway or failure of the CPU module
• Malfunction due to noise or other causes
• Hardware failure
• The devices outside the range was accessed
even though device checks are prohibited
(SM237 is on). (This error occurs only when any
of the BMOV, FMOV, or DFMOV instructions is
executed. (Universal model QCPU only))
■Collateral information
• Common information: -
• Individual information: Failure information
(QnUDVCPU only)
■Diagnostic timing
• Always
1001
[CPU UNIT DOWN]
Runaway or failure of the CPU module
• Malfunction due to noise or other causes
• Hardware failure
• The devices outside the range was accessed
even though device checks are prohibited
(SM237 is on). (This error occurs only when any
of the BMOV, FMOV, or DFMOV instruction is
executed.)
■Collateral information
• Common information: -
• Individual information: Failure information
■Diagnostic timing
• Always
308
List of error codes (1000 to 1999)
Corrective action
• Take noise reduction measures.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
• Take noise reduction measures.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
• Check the devices specified by BMOV,
FMOV, and DFMOV instructions and
correct the device settings. (Universal
model QCPU only)
• Take noise reduction measures.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
• Check the devices specified by BMOV,
FMOV, and DFMOV instructions and
correct the device settings.
LED status,
Corresponding
CPU status
QCPU
RUN: Off
ERR.:Flashing
CPU Status:Stop
LCPU
QCPU
RUN: Off
ERR.:Flashing
CPU Status:Stop
LCPU
CPU