4.3.2 I/O refresh (I/O module refresh processing)

4.3.3 Automatic refresh of the intelligent function module

4.3.4 END processing

4 - 11
In I/O refresh, an input (X) is received from the input module/intelligent function
module, and output (Y) of the Basic model QCPU is produced to the output
module/intelligent function module.
The I/O refresh is executed before the sequence program operation starts.
During constant scan execution, the I/O refresh is executed after the constant scan
delay time has elapsed.
(The I/O refresh is executed at each constant scan cycle.)
When automatic refresh of intelligent function modules is set, communication with the
intelligent function modules of the designated data is performed.
Refer to the manual for the intelligent function modules to use for details regarding of
the automatic refresh setting of intelligent function modules.
This is a post-processing to return the sequence program execution to step 0 after
completing the whole sequence program operation processing once.
• MELSECNET/H or CC-Link refresh processing
• Automatic refresh of intelligent function module
• Self-diagnostics
• Communication with external device such as GX Developer
• Processing of intelligent function module dedicated instruction