Mitsubishi Q-Series User Manual page 19

Programmable logic controller
Hide thumbs Also See for Q-Series:
Table of Contents

Advertisement

3 HARDWARE SPECIFICATION OF THE CPU MODULE
Item
Internal relay [M]
Latch relay [L]
Link relay [B]
Timer [ T ]
Retentive timer [ ST ]
Counter [C]
Data register [D]
Link register [W]
Annunciator [F]
Edge relay [V]
[R]
File Register
[ZR]
3 - 2
Performance Specifications (continued)
Q00JCPU
Default 8192 points (M0 to 8191)
Default 2048 points (L0 to 2047)
Default 2048 points (B0 to 7FF)
Default 512 points (T0 to 511) (for low / high speed timer)
Select between low / high speed timer by instructions.
The measurement unit of the low / high speed timer is set
with parameters.
(Low speed timer
: 1 to 1000ms, 1ms/unit , default 100ms)
(High speed timer
: 0.1 to 100ms, 0.1ms/unit , default 10ms)
Default 0 point
(for low / high speed retentive timer)
Switchover between the low / high speed retentive timer is
set by instructions.
The measurement unit of the low speed retentive timer and
high speed retentive timer is set with parameters.
(Low speed retentive timer : 1 to 1000ms, 1ms/unit , default 100ms)
(High speed retentive timer : 0.1 to 100ms, 0.1ms/unit , default 10ms)
• Normal counter default 512 points (C0 to 511)
• Interrupt counter maximum 128 points
(default 0 point, set with parameters)
Default 11136 points (D0 to 11135)
Default 2048 points (W0 to 7FF)
Default 1024 points (F0 to 1023)
Default 1024 points (V0 to 1023)
None
None
Model
Q00CPU
Q01CPU
32768 points (R0 to 32767)
32768 points (ZR0 to 32767)
MELSEC-Q
Remark
3
Number of use points
is set with
parameters.
3 - 2

Advertisement

Table of Contents
loading