8.4.8

Menu: Device Info

IMPORTANT (NOTE)
This menu is only used to display the device parameters. The parameters are displayed independently of the
configured access level, but cannot be changed.
... / Device Info
Menu / Parameter
Value range
Hardware Rev.
Software Rev.
Mounting Date
Commun. Tag
1)
Long Tag
Device Address
Descriptor
Device Message
Pneumatic Type
Single / Safe
Singe / Freeze
Double / Safe
Double / Freeze
Stroke Time Up
0 ... 200 s
Stroke Time Dn
0 ... 200 s
1) Only visible with HART7
Description
The hardware revision is displayed here.
The firmware revision is displayed here.
The installation date is displayed here. The date can only be entered and changed using a PC
(DTM / EDD).
The communication name is displayed here. The name can only be entered and changed using a
PC (DTM / EDD).
The long text for the measuring point tag is displayed here.
The measuring point tag for the valves and fittings is displayed here. The tag can only be entered
and changed using a PC (DTM / EDD).
The measuring point description is displayed here. The description can only be entered and
changed using a PC (DTM / EDD).
The device information is displayed here. The description can only be entered and changed using
a PC (DTM / EDD).
The type of pneumatics that the device works with is displayed here.
After installing a different type of pneumatics, this type needs to be set in the "Service >
Pneumatic" menu.
Single / Safe – Single-acting, safety position with no current, with fail-safe function.
Single / Freeze – Single-acting, safety position with no current, with fail-freeze function.
Double / Safe – Double-acting, safety position with no current, with fail-safe function.
Double / Freeze – Double-acting, safety position with no current, with fail-freeze function.
CAUTION – Risk of crushing!
If Service Mode is set to "On", the valve moves to its pneumatic safety position. In
the case of the "fail-safe" safety position, the valve moves to the end position in
an uncontrolled manner and / or no longer follows the setpoint current.
The actuator will therefore move without delay.
Do not reach into the adjustment mechanism.
The stroke time determined by Autoadjust (only Autoadjust types "Stroke" and "Full") for the
direction of the 100 % position is displayed here.
The stroke time determined by Autoadjust (only Autoadjust types "Stroke" and "Full") for the
direction of the 0 % position is displayed here.