Menu: Display - ABB PositionMaster EDP300 Operating Instruction

Electro-pneumatic positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

END STOP BEHAV.
... / .../ END STOP BEHAV.
Menu / Parameter
Value range
Tight Shut 0%
0 ... 45.0
Control at 0%
On, OFF
Dead Angle 0%
0.0 ... 45.0 %
Tight Shut 100%
55.0 ... 100
Control at 100%
On, OFF
Dead Angle 100%
55.0 ... 100.0 %
8.4.3

Menu: Display

.../ Display
Mask contents
Value range
ENGINEERING UNITS
Temperature
Pressure
Universal Input
Display Value
Position %
Position °
Setpoint %
Setpoint mA
Deviation %
Temperature
Univ. Inp.
Press. Y1
Press. Y2
Diff. Press.
Supply Press.
Contrast
0 ... 100 %
36 OI/EDP300-EN | PositionMaster EDP300
Description
The shut-off value is a percentage of the working range from which the 0 % position is
approached. Once the specified position limit value is reached, the actuator moves directly into
the 0 % end position.
Use this parameter to set the end position behavior. If the parameter is activated, the 0 % position
is controlled. Otherwise, the actuator moves into the 0 % mechanical end position.
Use this parameter to cut off the unusable range of the valve flow characteristic curve from the
point of view of control.
The dead angle is a percentage of the working range to which the valve is moved if the input
signal is 4.16 mA.
The shut-off value is a percentage of the working range from which the 100 % position is
approached. Once the specified position limit value is reached, the actuator moves directly into
the 100 % end position.
Use this parameter to set the end position behavior. If the parameter is activated, the 100%
position is controlled. Otherwise, the actuator moves into the 100% mechanical end position.
Use this parameter to cut off the unusable range of the valve flow characteristic curve from the
point of view of control.
The dead angle is a percentage of the working range to which the valve is moved if the input
signal is 19.84 mA.
Description
Use this parameter to select the units to be displayed.
Temperature:
°C – degrees Celsius
°F – degrees Fahrenheit
°R – degrees Rankine
K - Kelvin
Pressure:
psi
bar
kPa
Mpa
Universal Input:
The unit can only be entered in plain text using a DTM / EDD.
Use this parameter to select which value is to be shown on the process display.
Position – Position in %
Position ° - Position in degrees
Setpoint % - Setpoint in %
Setpoint mA – Setpoint in mA
Deviation – Control deviation in %
Elec.Temp. - Device temperature
Univ. IN – Scaled value at universal input
Press. Y1 – Pressure, output 1
Press. Y2 – Pressure, output 2
Diff. Press. – Differential pressure between the outputs
Supply Press. - Supply air pressure
Display contrast