alarm

alarm

Clearing alarms

Note: For more recent versions of the shelf manager firmware, ALLOW_CLEARING_CRITICAL_ALARM is set
to TRUE by default and the clia alarm clear command also clears critical alarms.
Note: Clearing the alarm changes the information displayed by the clia alarm command but not the
information displayed by the clia alarm info command.
34
clia alarm [clear | info| minor | major | critical]
This command provides access to the TELCO alarm outputs.
Enter clia alarm without parameters to view the current status of TELCO alarm
outputs:
# clia alarm
Pigeon Point Shelf Manager Command Line Interpreter
alarm mask: 0x00
Alarm mask 0x00 means no alarm.
Enter clia alarm clear to clear the minor and major alarm outputs. By default, critical
alarm outputs cannot be cleared. However, the shelfman.conf file contains the
following lines:
# ALLOW_CLEARING_CRITICAL_ALARM: This parameter of boolean type
enables the
# ability to clear the critical alarm condition without the
alarm cutoff
# button. Default is FALSE.
#
ALLOW_CLEARING_CRITICAL_ALARM = FALSE
If you change ALLOW_CLEARING_CRITICAL_ALARM to TRUE you can use the clia
alarm clear command to clear critical alarms.
Enter clia alarm info to display information about the last alarm that occurred:
# clia alarm info
Pigeon Point Shelf Manager Command Line Interpreter
Last saved alarm information:
Alarm mask: 0x00
Alarm date/time: Sun Jun 8 21:56:47 2009
Alarm source: Schroff Carrier
Alarm reason: Cooling state alert