Operating hours for heating mode, hot
water handling mode, cooling mode and
the overall operation

5.8 Setting the language

Menu → Basic settings → Language
– Setting the desired language

6 Maintenance and care

6.1 Checking and maintaining

6.1.1 Fulfilling requirements for the
installation site
The installation site must be dry and frost-
proof throughout.
Conditions: Outdoor air heat source
The air/brine collector is designed to be
operated with outdoor air. The air intake
and blow-off route of the outdoor unit must
be kept clear at all times in order to guar-
antee that the air can flow unhindered and
as intended. Vegetation and, in winter,
snowfall, must be cleared.
You are not permitted to make any sub-
sequent structural alterations which
may result in a reduced room volume
or a change to the temperature at the
installation site.
6.1.2 Caring for the product
Caution.
Risk of material damage
caused by unsuitable clean-
ing agents.
Do not use sprays, scouring
agents, detergents, solvents
or cleaning agents that con-
tain chlorine.
Clean the casing with a damp cloth and
a little solvent-free soap.
0020213396_00 flexoTHERM Operating instructions
Maintenance and care 6
6.1.3 Checking the system pressure
Check the filling pressure of the heating
installation every day for a week after
initial start-up and maintenance work,
and then twice a year.
– Filling pressure: ≥ 0.07 MPa
( ≥ 0.70 bar)
Filling pressure too low
Inform your competent person so
that he can add heating water and
increase the filling pressure.
6.1.4 Checking the brine circuit's
filling pressure
Check the brine circuit's filling pressure
at regular intervals. Read the brine cir-
cuit's filling pressure in the heat pump's
display.
– Brine fluid operating pressure range:
0.07 ... 0.20 MPa (0.70 ... 2.00 bar)

7 Troubleshooting

7.1 Fault message

If several faults occur at the same time,
the display shows the corresponding fault
messages for two seconds each in alterna-
tion.
F.714 Environment circuit: Pressure too
low
If the filling pressure falls below the min-
imum pressure, the heat pump will be
switched off automatically.
– Minimum brine fluid pressure:
≥ 0.05 MPa ( ≥ 0.50 bar)
– Min. brine fluid operating pressure:
≥ 0.07 MPa ( ≥ 0.70 bar)
Inform your competent person so that
he can top up the brine fluid.
F.723 Building circuit: Pressure too low
If the filling pressure falls below the min-
imum pressure, the heat pump will be
switched off automatically.
13