Omron C200H Operation Manual page 57

Analog i/o units
Hide thumbs Also See for C200H:
Table of Contents

Advertisement

Specifications
C200H-DA002 Analog Output Unit
All general specifications of the C200H-DA002 Analog Output Unit conform to those of the C Series.
Item
Number of analog outputs
Output signal range
Max. output impedance
Max. output current
Max. load resistance
Resolution
Set data
Accuracy
Conversion time (see Note)
Isolation
External connections
Power consumption
Dimensions
Weight
Note This is the time from after the data has been written to the Unit until an analog output appears. The output
data will not be correct if output data is rewritten faster than it can be output.
4
Voltage outputs
–10 to +10 V
Current outputs
4 to 20 mA
Voltage output: 0.5 Ω
Voltage output: 10 mA
Current output: 350 Ω
Voltage outputs
1/8190 max. (full scale)
Current outputs
1/4095 max. (full scale)
Voltage output: Sign bit +12-bit binary (8FFF to 0FFF)
Current output: 12-bit binary (0000 to 0FFF)
°
Voltage outputs: ±0.3% max. (full scale)
25
C
Current outputs: ±0.5% max. (full scale)
°
°
Voltage outputs: ±0.5% max. (full scale)
0
to 55
C
Current outputs: ±1.0% max. (full scale)
2.5 ms max./point
Between output terminals and PC: photocoupler
Between output terminals: none
19-pin terminal block (removable)
600 mA max. at 5 VDC
34.5 x 130 x 128 (W x H x D) mm (see last page of this appendix)
320 g max.
Specifications
Appendix B
49

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ad002Da002

Table of Contents