Omron C200H Operation Manual page 31

Analog i/o units
Hide thumbs Also See for C200H:
Table of Contents

Advertisement

Functions and Programming
2-3-3 Conversion Data Type Setting
Function
Setting Method
A/D Conversion Data
Binary Data Conversion
0 V
Inputs
Inputs 1 to 4
Inputs 5 and 6
Inputs 7 and 8
DM (m + 1)
Set DM word m+1 to "50AA" to set the desired input signal ranges.
Sets whether the digital conversion data is output in binary or BCD. The digital
data is output to IR words n+1 through n+8.
The scaling and square root functions can process BCD data only, so the data
type setting is ignored when these functions are being used.
Set the data type with bit 8 of DM word m.
The following table shows the range of data that is output to IR words n+1
through n+8.
Input range
0 to +10 V,
0000 to 0FA0
+1 to +5 V,
+4 to +20 mA
–10 to +10 V
87D0 to 8001, 0000 to 07D0
(–07D0 to –0001, 0000 to 07D0)
Note When the input range is set to –10 V to +10 V, the 15
status of 0 indicates "+" and a bit status of 1 indicates "–." There is no sign bit
when the scaling or square root function is being executed.
0 to +10 V
+1 to +5 V/+4 to +20 mA
+10 V
+1 V
+5 V
+4 mA
+20 mA
Input signal
Input signal range
+1 to +5 V
–10 to +10 V
0 to +10 V
Bit 15
01
01
00
5
0
É É É É
Bit 15
DM m
É É
Binary data
–10 to +10 V
–10 V
Sign bit (15
Section 2-3
Bit settings
10
00
01
00
00
10
10
10
10
A
A
08
00
0: Binary data
1: BCD data
BCD data
0000 to 4000
A000 to 8001, 0000 to 2000
(–2000 to –0001, 0000 to 2000)
th
bit indicates the sign. A bit
0
+10 V
Input signal
th
bit)
21