Wiring A Sounder Base; Wiring The W-Gate; 1: Slc Connections - Honeywell SLC Installation Manual

Intelligent control panel
Table of Contents

Advertisement

Intelligent Detector Bases and Wireless Gateway

9.6 Wiring a Sounder Base

Figure 9.4 shows typical wiring of the B200SR or B200SR-LF Sounder Base.
NOTE: For more detailed wiring on the sounder base, refer to the device's installation instructions.

9.7 Wiring the W-GATE

NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the
Federal Communications Commission (FCC) requirements of the United States Government. It
has not been evaluated for use outside the USA. Use of this system outside the USA is subject to
local laws and rules to which this product may not conform. It is the sole responsibility of the user
to determine if this product may be legally used outside the USA.
NOTE: It is recommended to use the same wire gauge if there are multiple connections to the
same terminal.
9.7.1 SLC Connections
The W-GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and a
LiteSpeed SLC loop on the MS-9200UDLS. It is powered by the SLC loop or by a regulated,
external 24VDC UL-listed power supply. Available wireless devices include a photo detector, a
photo/heat detector, a fixed-temperature heat detector, a rate-of-rise heat detector, and a monitor
module. For details about wireless devices, system setup, and operation, see the SWIFT™ Smart
Wireless Integrated Fire Technology Instruction Manual.
62
To next device
on SLC
+ -
+ -
SLC
Figure 9.4 Wiring of a B200SR/B200SR-LF Sounder Base
Note: The "grid" pattern on the
sounder base has been removed
for illustration purposes only.
+ -
UL-Listed
24V Power
Supply
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Wiring a Sounder Base
Optional Sounder
Interconnect