Description of the boiler

Condensing
Retrieves heat as much
as possible from the flue
gasses. Water condenses on
the heat exchanger.
Modulating
Stepless higher or lower
burning according to the heat
demand.
8
a. In the event that the side wall horizontally vented gas fueled equipment is installed
in a crawl space or an attic, the hard wired carbon monoxide detector with alarm
and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time
of completion of installation, the owner shall have a period of thirty (30} days to
comply with the above requirements; provided, however, that during said thirty
(30} day period, a battery operated carbon monoxide detector with an alarm shall
be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide
detector as required in accordance with the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
The Rinnai E-Series System boiler is a modulating condensing central heating boiler.
The boiler is provided with a compact stainless steel heat exchanger with smooth
tubes.
The boiler burns gas to supply heat. The heat is transferred in the heat exchanger
to the water in the central heating system. By cooling down the exhaust gases
condensate is formed. This results in high efficiency. The condensate, which has
no effect on the heat exchanger and the function of the boiler, is drained through a
condensate collector trap.
The boiler is provided with an intelligent control system (CMS Control Management
System). The boiler anticipates the heat demand of the central heating system.
When an outdoor sensor is connected to the boiler it will operate weather dependantly
using outdoor reset. This means that the boiler control measures the outside
temperature and supply temperature. With this data the boiler calculates the optimal
supply temperature for the installation. Outdoor reset lowers the boilers heating supply
temperature when the weather is warmer, matching the heat loss of the building and
maximizing efficiency.
Explanation of the appliance type:
E = Type
110 = Nominal load in (x1000) BTU
S = System (Heat only)
N = Natural Gas (P = Propane Gas)
Different boilertypes:
System boiler (Heat only)
E60SRN
E60SRP
E85SRN
E85SRP
E110SRN
E110SRP
Rinnai E110SRN