Test Run; Preparing For Test Run; Indoor Units (Type E2, E1); Caution - Panasonic S-200PE2E5 Technical Data & Service Manual

Dc inverter
Table of Contents

Advertisement

2-1. Preparing for Test Run

Before attempting to start the air conditioner, check the following:
(1) All loose matter is removed from the cabinet especially
steel filings, bits of wire, and clips.
(2) The control wiring is correctly connected and all
electrical connections are tight.
2
(3) The protective spacers for the compressor used for
transportation have been removed.
If not, remove them now.
(4) The transportation pads for the indoor fan have been
removed. If not, remove them now.
(5) The power has been supplied to the unit for at least 5
hours before starting the compressor. The bottom of
the compressor should be warm to the touch and the
crankcase heater around the feet of the compressor
should be hot to the touch. (Fig. 2-1)
(6) Both the gas and liquid tube service valves are open.
If not, open them now. (Fig. 2-2)
(7) Request that the customer be present for the test run. Explain the contents of the instruction manual, and then
have the customer actually operate the system.
(8) Be sure to give the instruction manual and warranty certificate to the customer.
(9) When replacing the control PCB, be sure to make all the same settings on the new PCB as were in use before
replacement. The existing EEPROM is not changed, and is connected to the new control PCB.

Indoor Units (Type E2, E1)

2-2. Caution

This unit may be used in a
single-type refrigerant system
where 1 outdoor unit is
connected to 1 indoor unit.
The indoor and outdoor unit
control PCB utilizes a
semiconductor memory
element (EEPROM).
The settings required for
operation were made at the
time of shipment.
Only the correct combinations
of indoor and outdoor units
can be used.
This test run section describes
primarily the procedure
when using the wired remote
controller.
2-3. Test Run Procedure
Recheck the items to check before the test run.
Check the combination (wiring) of indoor and outdoor units.
Is system "single-type"?
YES
(1 indoor unit is connected to 1 outdoor unit
and remote controller)
Is group control with
multiple outdoor units used?
Turn ON the
indoor and
outdoor power.
Turn ON the indoor and outdoor power.
(Automatic
Address)
(*1)
Indicate (mark) the combination number.
Set the remote controller to "test run".
operation be
Return the remote controller to normal control.
2-2
ON
(Power must be turned ON at least
5 hours before attempting test run)
Power mains switch
Liquid tube
NO
YES
NO
Automatic address
(See 2-8-5)
(See 2-5)
Refer to "Table of Self-Diagnostic
Functions" to check the system.
NO
Can
In addition, refer to 2-8-1 to 5 and
started?
correct any items that need to be
corrected.
YES
Note: Check the indoor-side drainage.
(*1) Required for simultaneous-operation
multi systems and for group control.
Fig. 2-1
Gas tube
Fig. 2-2
(See 2-4)
(See 2-8-1 to 5)
(See 2-8-3)
Setting the Outdoor
Unit System
Address
Set the outdoor
unit system
address.
(See 2-8-4)
Automatic Address
Setting
Use the remote
controller to
perform automatic
address setting.
Fig. 2-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents