Check Of Limit Density - Panasonic S-200PE2E5 Technical Data & Service Manual

Dc inverter
Table of Contents

Advertisement

1.
CAUTION
2.
Always check the gas density
WARNING
for the room in which the unit is
installed.
2.
Chec
k of limit density
When installing an air conditioner in a room, it is
necessary to ensure that even if the refrigerant gas
accidentally escapes, its density does not exceed the
limit level.
If the density might exceed the limit level, it is
necessary to set up an opening between it and the
adjacent room, or to install mechanical ventilation
which is interlocked with a leak detector.
(Total refrigerant charged amount: kg)
(Min. indoor volume where the indoor unit is installed: m³)
< Limit density 0.3 (kg/ m
The limit density of refrigerant which is used in this
3
unit is 0.3 kg/m
(ISO 5149).
The shipped outdoor unit comes charged with the
amount of refrigerant fi xed for each type, so add it
to the amount that is charged at the fi eld. (For the
refrigerant charge amount at shipment, refer to the
unit's nameplate.)
This unit requires no additional refrigerant
charge up to tubing length 30 m. In case
of more than 30 m, additional refrigerant
charge is required. Refer to Tables 1-1 and
1-3.
In case of multi type installation, indoor
units should be installed within the
same room. If multi type indoor units are
installed in different rooms, temperature
control may develop problems because
thermostat operation must follow the
thermostat condition of 1 indoor unit only
(the main unit).
3
)
Minimum indoor volume & fl oor area relative to the
amount of refrigerant are roughly as given in the
following table.
2
3
m
m
50
135
Range below
45
121.5
the density limit
of 0.3 kg/m
40
108
(countermeasures
not needed)
35
94.5
30
81.0
25
67.5
20
54.0
15
40.5
10
27.0
5
13.5
CAUTION
1-37
3
Range above
the density limit
of 0.3 kg/m
(countermeasures
needed)
10
20
30
40 kg
Total amount of refrigerant
Pay special attention to any
location, such as a basement
or recessed area, etc. where
leaked refrigerant can
collect, since refrigerant gas
is heavier than air.