1.4 Notes on the application

1.4.1 Installation

Installation environment

• Operate in areas where ambient temperature ranges from
–10°C to 50°C.
Where ambient temperature will rise above 40°C, derating
of rated current is needed.
• Install the inverter in a well-ventilated place and mount it
on a flat metal plate in portrait operation.
1
• Leave a space of 10cm or more on the upper and lower
sides of the inverter, and a space of 5cm or more on each
side.
• This inverter have a structure with IP54 conformity.
IP54 is a structure that protects the contents from dust and
harmful effects of water that drops from every direction.
How to install
Derating curves
Derating curves in E6581386 manual are only for standard models. For totally enclosed box type, refer to following
derating curves.
0.75~2.2, 30kW
7.5, 11kW
5cm or more
3.7, 5.5kW
15~22, 37~90kW
A-14
E6581429
10cm or more
VF-PS1
5cm or more
10cm or more