c. If subcooling and superheat are high, adjust TXV valve superheat, then check subcooling.
d. If subcooling is high and superheat is low, adjust TXV valve superheat and remove charge to lower the subcooling.
NOTE: Do NOT adjust the charge based on suction pressure unless there is a gross undercharge.
4. Disconnect manifold set, installation is complete.
Refrigerant Charge Check (Units with Fixed Orifice Devices)
After completing airflow measurements and adjustments the unit's refrigerant charge must be checked. All package units with
fixed orifice devices are charged using the super heat method at the compressor suction line.
After superheat is adjusted it is recommended to check unit sub-cooling at the condenser coil liquid line out. For charge adjustments,
see superheat and subcooling charts shown for each model.
S
C
H
YSTEM
HARGING
EATING
The proper method of charging a heat pump in the heat mode is by weighing the charge according to the total charge listed on the
rating plate.
SUPERHEAT = SUCTION LINE TEMP - SAT. SUCTION TEMP
SATURATED SUCTION PRESSURE
SUCTION PRESSURE
PSIG
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
85
90
95
100
110
120
130
140
150
160
170
Measure the hot gas discharge at the compressor to ensure proper TXV setting. To ensure optimum system performance in heat
mode, the TXV may require adjustment.
1. Allow the system to operate for at least 20 minutes.
2. Attach and insulate an electronic thermometer to the hot gas discharge
line mid-way between the compressor and the reversing valve.
NOTE: The thermometer must be well insulated to prevent ambient
influences.
3. Allow the compressor to operate for about 10 additional minutes and
measure the hot gas discharge temperature.
4. Using an additional electronic thermometer, measure the ambient
temperature.
5. Adjust the TXV until the hot gas temperature equals 100°F + ambient
temperature (+ or - 3°F). Close TXV to increase the temperature.
NOTE: When adjusting the TXV, allow the compressor to operate for
about 10 minutes before taking readings. Do not adjust TXV more
than 1/4 of a turn between readings.
M
ODE
TEMPERATURE CHART
SATURATED SUCTION
TEMPERATURE ºF
R-410A
1
3
4
6
7
8
10
11
13
14
15
16
17
19
20
21
24
26
29
31
36
41
45
49
53
56
60
SUBCOOLING = SAT. LIQUID TEMP. - LIQUID LINE TEMP.
SATURATED LIQUID PRESSURE
LIQUID PRESSURE
Design Superheat & Subcooling
@ 95
F Outdoor Ambient Temperature
°
Models
GPH1624M41
GPH1630M41
GPH1636M41
GPH1642M41
GPH1648M41
13
TEMPERATURE CHART
SATURATED LIQUID
TEMPERATURE ºF
PSIG
R-410A
200
70
210
73
220
76
225
78
235
80
245
83
255
85
265
88
275
90
285
92
295
95
305
97
325
101
355
108
375
112
405
118
415
119
425
121
435
123
445
125
475
130
500
134
525
138
550
142
575
145
600
149
625
152
High Stage
Superheat °F
Subcooling °F
15 ±2
15 ±2
13 ±2
15 ±2
15 ±2
8 ±2
10 ±2
10 ±2
10 ±2
13 ±2