Technical data
6.2 Output
Number of units connected in parallel
to increase the power rating, units
Output characteristic
Output
Rated voltage value Ua rated
DC
Total tolerance, static ±
Static line regulation, approx. 2 %
Static load regulation,
approx.
Residual ripple in the load
range peak-peak, max.
Spikes peak-peak, max.
(bandwidth, approx. 20 MHz)
Adjustment range
Product function / output
voltage can be adjusted
Output voltage setting
Remark
•
Operating display
Signaling
Response when switching
on/off
Starting delay, max.
Voltage rise, typ.
Voltage rise time of the
output voltage, maximum
Rated current value Ia rated
Current range
Remark
•
Output active power /
typical
Constant overload current
for a short-circuit when
powering up, typical
42
6EP1436-3BA10 (24 V/20 A)
2
See Figure 6-3 6EP1436-3BA10 single
operation output characteristic curve
(Page 44)
6EP1424-3BA00
(12 V / 20 A)
Regulated, isolated DC
voltage
12 V
3 %
4 %
100 mV
200 mV
12 ... 14 V
Yes
Via potentiometer
-
LED green for "12 V O.K."
Relay contact (NO contact,
rating 60 V DC / 0.3 A) for
"12 V O.K."
No overshoot of Ua
(Soft-Start)
2.5 s
20 ms
500 ms
20 A
0 ... 20 A
20 A to +70° C
240 W
22 A
6EP1456-3BA00 (48 V/10 A)
2
See Figure 6-4 6EP1456-3BA00 single
operation output characteristic curve
(Page 44)
6EP1436-3BA20
(24 V / 17 A)
Regulated, isolated DC
voltage
24 V
3 %
0,1 %
0,2 %
100 mV
200 mV
24 ... 28.8 V
Yes
Via potentiometer
Max. 480 W
LED green for "24 V O.K."
Relay contact (NO contact, rating 60 V DC / 0.3 A) for
"24 V O.K."
No overshoot of Ua
(Soft-Start)
2.5 s
40 ms
500 ms
20 A
0 ... 17 A
14 A to +70 °C
408 W
19 A
Manual, 11.2014, C98130-A7574-A2-2-7629
6EP1437-3BA20
(24 V / 30 A)
Regulated, isolated DC
voltage
24 V
3 %
0,1 %
0,1 %
100 mV
200 mV
24 ... 28.8 V
Yes
Via potentiometer
-
LED green for "24 V O.K."
No overshoot of Ua
(Soft-Start)
2.5 s
20 ms
500 ms
30 A
0 ... 30 A
25 A to +70° C
720 W
32 A
SITOP PSU300M/300B