Eaton 9315/9390/9395 Fixed Master Sync Control Installation and Operation Manual
Perform the following procedure to set up the Eaton Fixed Master Sync Control for
operation with your system. See Figure 4‐2 and Table 4‐1 for the location and
explanation of the controls and indicators on the Eaton Fixed Master Sync Control.
1.
Place the non-master system in normal operating mode. Refer to the applicable
UPS installation and operation manual listed in paragraph 1.3 on page 1-4.
2.
Press the LAMP TEST pushbutton to verify all indicators illuminate and are
working correctly.
3.
Depress the LOAD SYNC ENABLE pushbutton switch to enable the automatic
synchronization control. The pushbutton illuminates when the synchronization
control is activated.
4.
To disable the automatic synchronization control, depress the LOAD SYNC
ENABLE switch and verify the LOAD SYNC ENABLE pushbutton is extinguished.
Figure 4‐2. Eaton Fixed Master Sync Control Controls and Indicators
S
P-164000023 Rev 1 www.eaton.com/powerquality
OPERATION
4-3