Outdoor Fan - Payne PA3Z Installation Manual

Single packaged air conditioner
Table of Contents

Advertisement

UNIT SIZE
600
700
024
.027
.034
030
-
.036
036
-
-
042
-
-
048
-
-
060
-
-
UNIT SIZE
FILTER SIZE (IN.)
024-036
24 x 24
042-060
30 x 30
UNIT SIZE
FILTER SIZE (IN.)
024-036
24 x 24
042-060
30 x 30
HEATER KW
600
5-20
0.06
Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter
from the pan. Flush the pan and drain tube with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain tube
is restricted, clear it with a ''plumbers snake'' or similar probe device. Ensure that the auxiliary drain port above the drain tube is also clear.
PROCEDURE 5—OUTDOOR FAN
CAUTION: UNIT OPERATIONAL HAZARD
Failure to follow this caution may result in damage to unit components.
Keep the Outdoor fan free from all obstructions to ensure proper cooling operation. Never place articles on top of the unit.
1. Shut off unit power supply and install lockout tag.
2. Remove outdoor-fan assembly (grille, motor, motor cover, and fan) by removing screws and flipping assembly onto unit top cover.
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 12 or 13.
5. Tighten setscrews.
6. Replace outdoor-fan assembly.
PROCEDURE 6—ELECTRICAL CONTROLS AND WIRING
Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit and install lockout tag.
Remove the top panel to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections.
If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, restrip the wire end and reassemble the connection
properly and securely.
Check to ensure no wires are touching refrigerant tubing or sharp sheet metal edges. Move and secure wires to isolate from tubing and sheet metal
edges.
After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete cooling cycle to ensure
proper operation. If discrepancies are observed in operating cycle, or if a suspected malfunction has occurred, check each electrical component
with the proper electrical instrumentation. Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the Sequence of Operation section, as an aid in determining proper control operation.
PROCEDURE 7—REFRIGERANT CIRCUIT
Inspect all refrigerant tubing connections and the unit base for oil accumulations annually. Detecting oil generally indicates a refrigerant leak.
Table 9—Wet Coil Pressure Drop
STANDARD CFM (S.C.F.M.)
800
900
1000
1100
040
.047
.053
-
.042
.050
.055
.063
-
.050
.055
.063
-
-
.042
.049
-
-
-
-
-
-
-
-
Table 10—Filter Pressure Drop (in. wg)
500
600
700
0.06
0.07
0.08
-
-
-
1500
1600
0.14
0.15
0.10
0.11
Table 11—Accessory Electric Heat Pressure Drop
(in. wg)
800
1000
1200
0.08
0.10
0.13
1200
1300
1400
1500
-
-
-
-
.072
.081
-
-
.072
.081
.090
.097
.052
.059
.065
.071
.072
.081
.090
.097
-
-
-
.071
CFM
800
900
1000
0.08
0.09
0.09
-
-
-
CFM
1700
1800
1900
-
-
-
0.12
0.13
0.14
CFM
1400
1600
0.15
0.18
—19—
1600
1700
1800
1900
-
-
-
-
-
-
-
-
-
-
-
-
.078
.085
.091
-
.108
.120
.129
.139
.078
.085
.091
.098
1100
1200
1300
0.09
0.10
0.11
-
-
0.08
2000
2100
2200
-
-
-
0.15
0.16
0.17
1800
2000
0.20
0.23
2000
-
-
-
-
-
.114
1400
0.12
0.09
2300
-
0.18
2200
0.25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents