5.7.8 Output 1 Configuration (Command Index 0C)

Description: OUT1CNG.76543210 means 8 bit positions of the Command Data.
BIT NUMBER
7
6
5
4
0
1
0
1
0
1
Example: Set PID, Direct, Auto PID Enable, Anti Integral Enable, Auto PID Stop.
The command data is 00010111Bin = 2Fhex. Send: *W0C17

5.7.9 Output 2 Configuration (Command Index 0D)

Description: OUT2CNG.76543210 means 8 bit positions of the Command Data.
BIT NUMBER
7
6
5
4
0
0
0
0
0
1
0
1
0
0
1
1
1
0
0
1
0
1
1
1
0
1
1
1
0
1
Example: Set On/Off, Reverse, Auto PID Disable, Ramp Disable, Soak Disable,
Damping 4. The command data is 10000101Bin = 80Hex. Send: *W0D85
3
2
1
0
0
1
0
1
0
1
3
2
1
0
0
1
0
1
0
1
0
1
FUNCTION
Auto Tune PID Stop
Auto Tune PID Start
Anti Wind Up Disable
Anti Wind Up Enable
Auto PID Disable
Auto PID Enable
Reverse
Direct
Analog Proportional 0 – 20 mA
Analog proportional 4 – 20 mA
Time Proportional On/Off
Time Proportional PID
FUNCTION
Damping 0
Damping 1
Damping 2
Damping 3
Damping 4
Damping 5
Damping 6
Damping 7
Soak Disable
Soak Enable
Ramp Disable
Ramp Enable
Auto PID Disable
Auto PID Enable
Reverse
Direct
Time Proportional On/Off
Time Proportional PID