Selecting The Normal Sampling Rate - Honeywell XYR 5000 series User Manual

Wireless dual analog input interface transmitter
Hide thumbs Also See for XYR 5000 series:
Table of Contents

Advertisement

Honeywell Process Solutions
6.2: Selecting the Normal
Sampling Rate*
Figure 6.3: Incorrect Sampling Rate
Figure 6.4: Correct Sampling Rate
Rev. 8
July 2012
The Normal Sampling Rate is the interval in which the Transmitter reads
the monitored process value. As previously mentioned, the Transmitter is
in "sleep" mode to save power during the operations sequence. This mode
turns off most of the electronics on the unit (with the exception of the
LCD) in order to preserve battery life. The Transmitter will then 'wake up'
for every Normal Sampling Period and take the necessary process value
readings.
Notice that the minimum speed of the Normal Sampling Rate is dependent
on the Normal Transmission Rate setting selected (see Section 6.1). The
Sampling Rate cannot be set slower than the Normal Sampling Rate. Thus,
if you selected the Normal Transmit Rate setting to be 10 Seconds the
Normal Sampling Rate must be set to 10 seconds or faster. A complete
table of these parameters is shown below.
Baud Rate
(communication range)
(fastest speed of updates)
Normal and Abnormal
1 Second or Greater
Transmit Rates
Normal and Abnormal
Equal to Transmit
Sampling Rates
In order to properly set the Normal Sampling Rate, determine how often
updates are needed from the Transmitter when the process being moni-
tored is operating under normal conditions. The Transmitter has a select-
able range of 1-5, 10, 15, 20, 30, and 60 seconds depending on the Normal
Transmission Rate. The factory default is 1 second. However, the more
frequently the Transmitter wakes up to check the monitored device, the
faster you will use up the battery life of the Transmitter.
Figure 6.3 is an example of what happens when the Normal Sampling Rate
is too slow for the process being monitored. Notice how the rise in the
voltage level falls between two normal samples, and thus goes completely
undetected.
Figure 6.4 is an example of what happens when the Normal Sampling Rate
is correctly set for the device that is being monitored. Notice how this set-
ting makes it possible to sample the rise in the voltage level.
Once you have decided on the proper Normal Sampling Rate select this
setting from the Transmitter or through WMT.
Using Wireless Management Toolkit
If you have the Wireless Management Toolkit software this menu option
will not be accessible via the Transmitter once the Transmitter detects
that the software is being used (See Appendix A for more details). An
explanation of how to select the Normal Sampling Rate using the Wire-
less Management Toolkit software can be found in section 6.7.
* Indicates that Menu is Disabled if Wireless Management Toolkit is detected. (See Appendix A)
User Manual
Wireless Dual Analog Input Interface Transmitter
76.8K
19.2K
500-750 feet
2000-2500 feet
1 Second
5 Seconds
5 Seconds or
Greater
Equal to Transmit
Rate or Less
Rate or Less
4.8K
3000 feet
20 Seconds
20 Seconds or
Greater
Equal to Transmit
Rate or Less
23