Item
2. Indoor fan
<In heating operation> (Heat pump model)
motor control
HEAT ON
Fan speed setup
AUTO
YES
TC ³ 42˚C
NO
(Fig. 4)
Basic fan control
[ ˚C ]
TA
b
TSC
c
–0.5
d
–1.0
e
–1.5
f
–2.0
g
–2.5
–5.0
–5.5
*1: Fan speed = (M + –L) × 1
*2: Fan speed = (M + –L) × 2
*3: Fan speed = (M + –L) × 3
(Calculated with linear approximation from M+ and L)
(Fig. 5)
[In starting and in stability]
• Until 12 minutes passed after operation start
FAN AUTO
• When 12 to 25 minutes passed after operation
start and room temp. is 3°C or lower than set temp.
FAN Manual
• Room temp. < Set temp. –4°C
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
Operation flow and applicable data, etc.
MANUAL
Indication
L
L+
M
M+
H
Min air flow rate control
Limited to Min WD tap
Tc
52
51
*
42
41
No limit
* Fan speed =
(TC – (42 + a)) / 10 × (WD – W8) + W8
a : In up operation 1, in down operation 0
Fan speed
AUTO
L (W8)
*1
*2
*3
M+ (WD)
H (WE)
÷
4 + L
÷
4 + L
÷
4 + L
In starting
– 54 –
www.heronhill.co.uk
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is per-
formed with the constant speed
shown in Fig. 3 and Table 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
(Fig. 3)
controlled to the fan speed level
shown in Fig. 5 according to the set
temperature and room temperature.
Fan speed
3) Min air flow rate is controlled by
W8
temperature of the indoor heat
(L + M) / 2
exchanger (Tc) as shown in Fig. 4.
WA
4) Cold draft prevention, the fan
(M + H) / 2
speed is controlled by temperature
of the indoor heat exchanger (Tc)
WE
as shown in Fig. 6.
Cold draft preventive control
Tc
46
46
34
45
45
33
33
33
21
32
32
20
*A+4
*A+4
*A+4
*A-4
*A-4
*A-4
Fan speed MANUAL in starting
Fan speed AUTO in stability
Fan speed AUTO in starting
* No limitation while fan speed MANUAL mode is in stability.
* A: When Tsc ≥ 24, A is 24, and when Tsc < 24, A is Tsc
Tsc: Set value
(Fig. 6)
In stability
• When 12 to 25 minutes passed after operation start
and room temp. is higher than (set temp. –3°C)
• When 25 minutes or more passed after operation start
• Room temp. ≥ Set temp. –3.5°C
Description
H (WE)
Line-approximate
H and SUL with Tc.
SUL (W2)
Stop
Fax: 01823 665807