Operation of the module behind a PROFIBUS DP interface module
If the module is operated behind a PROFIBUS DP interface module, the parameter data
records 0 and 1 are not read back. You get the diagnostics data records 0 and 1 for the read
back parameter data records 0 and 1. You can find more information in the Interrupts section
of the PROFIBUS DP interface module device manual on the Internet
(http://support.automation.siemens.com/WW/view/en/78324181).
Assignment of data record and channel
The channel parameters in data records 64 to 67 are available for 1x 4-channel configuration
and are assigned as follows:
● Data record 64 for channel 0
● Data record 65 for channel 1
● Data record 66 for channel 2
● Data record 67 for channel 3
For configuration 4 x 1-channel, the module has 4 submodules with one channel each. The
parameters for the channel are available in data record 64 and are assigned as follows:
● Data record 64 for channel 0 (submodule 1)
● Data record 64 for channel 1 (submodule 2)
● Data record 64 for channel 2 (submodule 3)
● Data record 64 for channel 3 (submodule 4)
Address the respective submodule for data record transfer.
Analog output module AQ 4xU/I ST (6ES7532-5HD00-0AB0)
Manual, 09/2016, A5E03484696-AD
B.1 Parameter assignment and structure of the parameter data records
Parameter data records
33