Advanced Digital Control Operation; Controls And Indicators - Kohler 10ERG Operation Manual

Commercial mobile generator set
Hide thumbs Also See for 10ERG:
Table of Contents

Advertisement

2.4 Advanced Digital Control
Operation
Figure 2-2 illustrates the user interface on the Advanced
Digital Control (ADC 2100).
Note: Have setup and adjustments of the ADC 2100
performed only by an authorized Kohler
distributor/dealer. The setup and adjustments
are password protected.
1
4
1. LED display
2. Up and down arrow buttons (use for setup and adjustment
only)
3. Generator set master switch
4. Select button (use for setup and adjustment only)
Figure 2-2 ADC 2100 Control
Control or Indicator
Item
Runtime hours
LED display
p y
Crank indication
Fault codes
Software version
Keypad
Select and arrow
buttons
Generator set master
Three-position
switch
switch
Figure 2-3 ADC 2100 Controls and Indicators
4 Operation
2
3
GM28707A-C
Description
Displays total generator set runtime hours.
Displays CC_1, CC_2, or CC_3 to indicate the first, second or third attempt to start the
engine. The last digit flashes during the crank cycle rest periods.
Flashes a 2- or 3-letter fault code to indicate various fault conditions. See Section 2.4.4.
See TP-6335, Generator Set Installation Manual.
The keypad is used for controller setup and adjustment only. Have setup and adjustments
performed only by an authorized distributor/dealer. The setup and adjustment functions are
password-protected.
Switch functions as the generator set operation and controller reset switch.
2.4.1

Controls and Indicators

Figure 2-3 describes the controls and indicators located
on the controller. The LED display indicates generator set
status as shown in Figure 2-3. The display is active when
the master switch is in the RUN or AUTO position and
remains active until the generator set master switch is
moved to the OFF/RESET position or the power to the
controller is removed. If the factory-installed continuous
power mode jumper has been disconnected, the LED
display turns off 48 hours after the generator set
shutdown. See Section 2.4.6.
The buttons on the controller keypad are used only for
system configuration and adjustment. The controller is
factory-set and should not require configuration or
adjustment under normal operating conditions. If the
generator set is reconnected to a different voltage
and/or frequency, refer to an authorized Kohler
distributor/dealer
for
adjustment instructions.