Table 13- 6
Error types
Diagnostic message
Undervoltage
1
Overvoltage
Overload
High limit
Low limit
1
Error
Parameter assignment
error
Load voltage missing
Channel is temporarily
unavailable
If the "Undervoltage" and "Low limit" diagnostics are active at the same time, the "Low limit" diagnostics has higher
1
priority and deletes the "Undervoltage" diagnostics.
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA
Error code
Meaning
2
Line voltage (measuring range) is moni-
H
tored for tolerance. Violation leads to volt-
3
H
age overflow/underflow
4
The measured current is monitored after
H
expiration of the "Tolerance time" for "Tol-
erance factor × Measured current". Ex-
ceeding this results in overflow current.
The maximum value of the secondary
current (12 A) has been exceeded.
7
Cumulative overflow in the calculated val-
H
ues
8
Violation of the low limit for voltage meas-
H
urement. The message occurs when the
configured minimum current or voltage is
below 80 V.
9
Internal module error (diagnostic alarm on
H
channel 0 applies to the entire module).
10
The module cannot evaluate parame-
H
ters for the channel.
Incorrect parameter assignment.
11
Missing or insufficient line voltage on
H
phase L1
1F
Firmware upgrade is being performed.
H
Channel 0 applies to the entire module.
The module is currently not performing any
measurements.
A user calibration is being executed at the
channel.
Interrupts/diagnostic alarms
13.3 Diagnostic alarms
Solution
Observe the line voltage range
Observe the current range
-
Observe the voltage range
Replace the module
Correct the parameter assignment
Check supply
--
Complete the user calibration