User data variants
D.1 User data variants with 32 bytes input data / 12 bytes output data
Basic variables energy counter measurement (periodic) overflow counter (ID 239 or EF
Table D- 13
Basic variables energy counter measurement (periodic) overflow counter
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Overflow counter for active energy inflow L1
4 ... 5
Overflow counter for active energy outflow L1
6 ... 7
Overflow counter for reactive energy inflow L1
8 ... 9
Overflow counter for reactive energy outflow L1
10 ... 11
Overflow counter for apparent energy L1
12 ... 13
Overflow counter for active energy inflow L2
14 ... 15
Overflow counter for active energy outflow L2
16 ... 17
Overflow counter for reactive energy inflow L2
18 ... 19
Overflow counter for reactive energy outflow L2
20 ... 21
Overflow counter for apparent energy L2
22 ... 23
Overflow counter for active energy inflow L3
24 ... 25
Overflow counter for active energy outflow L3
26 ... 27
Overflow counter for reactive energy inflow L3
28 ... 29
Overflow counter for reactive energy outflow L3
30 ... 31
Overflow counter for apparent energy L3
146
I
U
I
U
I
U
1
3
3
2
2
1
1
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Data type
Unit
BYTE
-
BYTE
Bit string
UINT
-
UINT
-
UINT
-
UINT
-
UINT
-
UINT
-
UINT
-
UINT
-
UINT
-
UINT
-
UINT
-
UINT
-
UINT
-
UINT
-
UINT
-
Manual, 12/2015, A5E36061895-AA
)
H
Value range
Measured
value ID
239 (EFH)
-
qq xx xx xx
-
0 ... 65535
65120
0 ... 65535
65121
0 ... 65535
65122
0 ... 65535
65123
0 ... 65535
65124
0 ... 65535
62220
0 ... 65535
62221
0 ... 65535
62222
0 ... 65535
62223
0 ... 65535
62224
0 ... 65535
62320
0 ... 65535
62321
0 ... 65535
62322
0 ... 65535
62323
0 ... 65535
62324