Wiring
3.3 Current transformer selection data
Checking the ratio of burden load and power loss
The rated burden of the transformer must be 1.5 to 2 times greater than the power loss in the
connection circuit to ensure that the transformer is not overloaded and that the current
limitation is ensured during a short-circuit.
At a maximum secondary current of 4 A the power loss in the connection circuit is calculated
in accordance with the following formula for a connection cable (outgoing and incoming line)
with a length of 10 m and a cross-section of 1.0 mm
Meter of 25 mΩ:
The ratio of the rated burden and the power loss in the connection circuit thus amounts to:
The required ratio of rated burden and power loss in the connection circuit lies within the
required range. The transformer is dimensioned sufficiently large.