Cooling Mode; Heating Mode - WINTAIR WAW-24/INV Technical And Service Manual

Dc inverter air conditioners
Table of Contents

Advertisement

8
.
C
H
E
C
K
I
N
G
C
O
8
.
C
H
E
C
K
I
N
G
C
O
Test system flow

Cooling mode

Test system
pressure.Does the low
pressure normal at
service part ?
The pressure on the
low side.
The system wants
refrigerant.The service
people must be ration
refrigeran.Is the low
pressure rise ?
NO
The refrigerant system
blocked.Please check
the Capillary Tube or
electronic expansion
valve)Is it blocked?
yes
Unsolder the capillary tube
ASS'Y(or electronic expansion
valve).The capillary tube1 is blown
by N
.
2

Heating mode

Test system
pressure.Does the
high pressure normal
at service part ?
The pressure on the
low side.
The system wants
NO
refrigerant.The service
people must be ration
refrigerant .Is the high
pressure rise in heating
mode?
NO
If the pressure is close
to static pressure?
yes
4-way valve collude or
compressor exhaust every
ebb.
DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3
M
P
O
N
E
N
T
S
M
P
O
N
E
N
T
S
The pressure on the
high side.
Recharge refrigerant
after air purging with
the vacuum
pump.Does the low
pressure nomal over
again?
yes
Air remaining at the
refrigerant system.
yes
Recharge
refrigerant .
NO
Check check valve and 4-
way valve.
The pressure on the
high side.
Recharge refrigerant
after air purging with
the vacuum
pump.Does the high
pressure normal over
again?
yes
Air remaining at the
refrigerant system.
yes
Recharge refrigerant
NO
If the pressure is
close to static
NO
pressure?
yes
4-way valve collude or
compressor exhaust very
ebb.
NO
Remove the back
panel."see"the
capillary tube1 and
capillary tube2.Is it
defrosting?
yes
The capillary tube
blocked.Unsolder the
capillary tube ASS'Y.The
capillary tube1 and capillary
tube2 is blown by N
2
Check heat exchanger and
4-way valve.
NO
.
117