USE FIGURE 21 AS A REFERENCE FOR SETTING
JUMPER CONFIGURATIONS ON THE AIR HANDLER CONTROL.
S
Set desired Heating Mode Blower Speed jumper
pin.
S
Electric heat is stages by room thermostat. (AHC
comes with factory jumper between W1 to W2 and W2
to W3)
S
Refer to Air Handler Control Checkout flow diagram for
operation.
To enter electric heat mode
configuration, push and hold button
next to single character LED display
until dash symbol (solid bar)
appears, then release button.
Solid dash
starts
blinking on
single
character
LED
display
1.
AHC will start the indoor blower motor to the selected heat jumper speed setting and cycle the electric heat relays ON to automatically detect number of electric
heat sections. (Electric heat section may be wired to energize more than one element)
2.
AHC waits for maximum of ten seconds to detect electric heat 22 volt DC relay coils are energizing:
A
If relay coil current is detected within ten seconds, AHC will show a 1 on the single character LED display indicating that the first stage has been detected. As
each additional heat section is detected, single character LED display on the AHC will display that electric element number. (Example: Last number displayed
by the single character LED display is 3, the AHC is configured to operate three electric heat sections.)
B
If relay coil current is not detected within ten seconds, the AHC will exit the current active mode and resume operation with electric heat disabled.
3.
AHC will automatically exit current configuration mode when configuration is completed. To verify that the number of electric sections detected matches the
installed electric heat package, the field MUST CONFIRM that the last number the single character LED display before exiting the Configuring/Detection Mode
matches the number of installed electric heat sections. AHC stores the number of electric heat stages in non−volatile memory.
4.
After the detection is finished, unit will continue to operate for an additional 30 seconds.
NOTE
If AHC push button is pushed or power is cycled on AHC is unable to verify all 22 volt DC electric heat relay(s) were energized using electric heater
detection, configuration will be stopped. Configuration function must be repeated.
Configuring/Detecting Electric Heat Sections
IMPORTANT
All electric heat installations require the Air Handler Control (AHC) to be manually
configured to detect number of heat sections.
NOTE
All field replacement AHC will require configuring/detecting electric heat sections.
Standard
Yes
_
Push and hold button until the solid H symbol is displayed on the single
_
character LED display, then release button.
Figure 24. Heat Mode Selection
Which Heat
Mode?
S
S
Configuration
S
S
AHC in Idle Mode
(No heating cooling or
indoor fan operation)
Finished
Page 30
EVENHEAT
Set desired Heating Mode Blower Speed jumper
pin.
Install and wire discharge air temperature sensor.
Set desired Target Discharge Temperature jumper
pin. If jumper pin is missing or discharge air
temperature sensor is not detected, AHC defaults to
Standard Heat Mode. Target settings are 85, 100, 115
and 130ºF) .
Refer to EVENHEAT Operation flow diagram for
operation.
No
Turn room thermostat to OFF.