Section 8 Establishing Connection And Verifying The Iec 61850 Communication; Overview; Setting The Station Communication - ABB rec670 Commissioning Manual

Intelligent electronic device
Hide thumbs Also See for rec670:
Table of Contents

Advertisement

1MRK 511 360-UEN A
Establishing connection and verifying the IEC 61850 communication
Section 8
8.1
8.2
Bay control REC670 2.1 IEC
Commissioning manual
Establishing connection and verifying the
IEC 61850 communication

Overview

The rear OEM ports are used for:
process bus (IEC 61850-9-2LE) communication
substation bus (IEC 61850-8-1) communication.
For IEC 61850-8-1 redundant communication, both rear OEM ports are utilized. In
this case IEC 61850-9-2LE communication can not be used.
IEC 61850-9-2LE process bus communication is not supported in the
IED.

Setting the station communication

To enable IEC 61850 communication the corresponding OEM ports must be
activated. The rear OEM port AB and CD is used for IEC 61850-8-1 communication.
The rear OEM port CD is used for IEC 61850-9-2LE communication. For IEC
61850-8-1 redundant communication, both OEM port AB and CD are used
exclusively.
IEC 61850-9-2LE communication can only be used on OEM rear port
X311:C, D.
To enable IEC 61850 station communication:
1.
Enable IEC 61850-8-1 (substation bus) communication for port AB.
1.1. Set values for the rear ports AB.
Navigate to: Main menu/Configuration/Communication/Ethernet
configuration/LANAB:1
Set values for Mode, IPAddress and IPMask. Mode must be set to Normal.
Check that the correct IP address is assigned to the port.
1.2. Enable IEC 61850-8-1 communication.
Section 8
65

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 seriesRelion rec670

Table of Contents