Section 7
Establishing connection and verifying the LON communication
Table 14:
ADE Non group settings (basic)
Name
Operation
TimerClass
7.2
64
Path in the local HMI under Main menu/Configuration/Communication/SLM
configuration/Rear optical LON port
Values (Range)
Unit
Off
-
On
Slow
-
Normal
Fast
Path in the local HMI under Main menu/Configuration/Communication/SLM
configuration/Rear optical LON port
Table 15:
LON commands
Command
Command description
ServicePinMsg
Command with confirmation. Transfers the node address to the LON Network Tool.
Optical budget calculation for serial communication
with LON
Table 16:
Example
Maximum attenuation
4 dB/km multi mode: 820 nm - 62.5/125 um
0.3 dB/m plastic: 620 nm - 1mm
Margins for installation, aging, and so on
Losses in connection box, two contacts (0.75 dB/contact)
Losses in connection box, two contacts (1dB/contact)
Margin for repair splices (0.5 dB/splice)
Maximum total attenuation
Step
Default
-
Off
-
Slow
1MRK 511 360-UEN A
Description
Operation
Timer class
Distance 1 km
Distance10 m
Glass
Plastic
-11 dB
- 7 dB
4 dB
-
-
3 dB
5 dB
2 dB
1.5 dB
-
-
2 dB
0.5 dB
-
11 dB
7 dB