Condensate Connection - Viessmann Vitodens 100 Installation And Service Instructions Manual

Wb1a
Hide thumbs Also See for Vitodens 100:
Table of Contents

Advertisement

Installing the boiler and making all connections

Condensate connection

Vitodens 100 has an internal syphonic condensate trap.
A 722 mm plastic condensate pipe
Routing
The condensate pipe can terminate into any one of the following areas.
It is always the best practice to terminate the condensate pipe via an internal
waste system.
&
The pipe run should take the shortest practical route with a downward slope of
at least 2.5 ° (45 mm/m)
&
The external pipework should be insulated to prevent freezing
&
The pipework should terminate as close as possible to the ground or drain,
whilst still allowing the condensate to safely disperse.
&
The condensate pipe must be of non corrosive material, preferably plastic.
Note: ferrous materials or copper must not be used.
Installation steps
(cont.)
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents