Industry Canada Compliance; Emi And Environmental Type Tests - Siemens RUGGEDCOM RS900 Installation Manual

Hide thumbs Also See for RUGGEDCOM RS900:
Table of Contents

Advertisement

Chapter 6
Certification
Section 6.3

Industry Canada Compliance

CAN ICES-3 (A) / NMB-3 (A)
Section 6.4

EMI and Environmental Type Tests

The RS900 has passed the following EMI and environmental tests.
IEC 61850-3 Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
24
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Voltage Dips and Interrupts
Damped Oscillatory
Enclosure
Contact
Enclosure Air
Enclosure ports
Signal ports
+/- 4 kV @ 2.5 kHz
DC Power ports
AC Power ports
Earth
ground ports
Signal ports
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
DC Power ports
+/- 2 kV line-to-earth,
+/- 1 kV line-to-line
AC Power ports
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
Signal ports
DC Power ports
AC Power ports
Earth
ground ports
Enclosure ports
40 A/m continuous, 1000 A/m for 1 s
DC Power ports
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
AC Power ports
30% for 1 period, 60% for 50 periods
100% for 5 periods,
100% for 50 periods
Signal ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
Installation Guide
Test Levels
Severity Levels
+/- 8 kV
+/- 15 kV
20 V/m
+/- 4 kV
+/- 4 kV
+/- 4 kV
10 V
10 V
10 V
10 V
Industry Canada Compliance
RUGGEDCOM RS900
4
4
x
x
4
4
4
4
3
4
3
3
3
3
3