SEND/RECEIVE interface in the user program
4.4 Additional information
Solution
Note the following recommendations:
● Do not call communication program blocks cyclically in OB1!
Call up communication time-controlled in a suitable time OB. The call interval of this OB
should be significantly higher than the average cycle time of OB1.
● Set a minimum cycle time that is higher than the average runtime of OB1. This frees
resources for communication on the CPU. This is, for example, a solution for existing
applications when communication already takes place cyclically in OB1.
● If necessary, reduce the time taken for communication processing on the CPU by
changing the parameter "Scan cycle load from communication" of the CPU.
90
Configuring and commissioning S7 CPs for Industrial Ethernet
Configuration Manual, 09/2013, C79000-G8976-C182-13