INSTALLATION INSTRUCTIONS FOR MASONRY APPLICATION
WARNING: Before starting the installation, the masonry chimney
must be inspected by a qualifi ed chimney sweep.
The following requirements must be respected:
1. The chimney must be absolutely clear of any soot residue or creosote.
Check for cracks, loose or missing bricks that could inhibit correct
installation of the liner.
2. The clearance to combustible must be a minimum of 1" between the
outside of the masonry and any wood framing or loose insulation.
3. The chimney must be built in accordance with the current building
code.
4. No other appliance can be connected to the same chimney.
5. The clearances to combustible for these fi replace connectors are 2"
on the side and bottom and 16" at the top.
6. The connector parts are not necessary if the connection between the
insulated length and the stainless steel liner is done within the masonry
chimney.
Installation:
The chimney must be relined with a stainless steel liner model Tubinox
or Projet
®
SS
*
of the same diameter as the outlet of the fi replace. If a
stainless steel liner is used, see note below**.
For connection at a 30º angle, a special connector (BISUMA30
used to connect the liner to the insulated chimney.
* IMPORTANT NOTE - The use of a 45º connector (BISUMA
proved for use in Canada ONLY. Installations in the USA must use the
30º connector (BISUMA30
Alternate brand rigid stainless liner or stainless fl ex may be substituted but
**
must be listed to UL-1777 for US application and ULC-S635 for existing
masonry or ULC-S640M for new masonry applications in Canada. The steel
rigid or fl ex liner must be rated at 2100º F (1100º C).
Figure 33
20
*
).
High-Temp.
Cement
Insulation Pad and
Cover (BISUMA * )
3 Screws
* Insulated
Elbow ASHT+ *,
HT6103+ *,
or DuraTech
®
DTC
6' 8"
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Follow these steps:
1- Position the fi replace in its location. Temporarily install the ASHT+
elbow on the top of the fi replace and, using a level, mark with an oval
the location where the fl ue liner will enter the masonry chimney.
2- In the middle of the oval, drill a hole in the masonry chimney at 30º.
3- Increase the size of the hole until a 30º Tubinox
easily slipped through.
4- Slide the liner down from the top of the masonry chimney until you
reach the hole level.
5- Slip through the hole a 30º liner elbow and connect it to the liner.
6- Add a small liner section to the liner elbow which will allow the liner to
extend at least 12" (measured at the top of the liner) from the masonry
chimney.
7- Seal the opening around the liner with high temperature refractory
cement.
8- The next steps must be done in the following order:
See typical installation illustrated below.
A. Select the ASHT+
so that it will slide at least 2" over the liner section (You may need to
cut the liner for a better fi t).
®
*
B. Take that section and the BISUMA30
Make sure you have enough opening to be able to install the ASHT+
elbow without diffi culty.
C. Install the 30º elbow on the fi replace.
D. Slide the length section back down on the elbow and twist lock the
*
) must be
two together.
E. Pull the cover down over the length and install the insulation pad over
*
) is ap-
the liner; be careful to cover the liner completely.
F. Slide back the cover over the insulation and fi x it in place using the 3
metal screws supplied.
Fireplace
length that will fi t between the elbow and the liner
*
*
cover and slide it over the liner.
1" Clearance
Firestop
Tubinox * or Projet SS *
Stainless Steel Liner *
Tubinox * or Projet SS * Liner Must
Slide at Least 2" Inside Length *
Insulated
Length
Masonry Chimney,
New or Existing
*
Available from Security Chimneys™
**
Available from DuraVent
*
*
liner elbow can be
*
®