Vent Configuration: Horizontal Terminations Using Lp - Travis Industries 4237 Installation Manual

Hide thumbs Also See for 4237:
Table of Contents

Advertisement

26

Vent Configuration: Horizontal Terminations using LP

 The termination must fall within the shaded area shown in the chart below.
 A maximum of 3 elbows may be used. Only 1 elbow may be a horizontal elbow (see
illustration below).
 Horizontal terminations require the high-wind cap (58DVA-HC), vinyl standoff
(58DVA-VSS), and the horizontal termination shield (included with the fireplace).
The high-wind sconce cap is not allowed.
 Vertical terminations require the high-wind cap (58DVA-VCH).
40' (12m) max
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
Exhaust Restrictor
Position # 2
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
Min. 2' (0.61m) Vertical Section Directly Off Fireplace Required
0 feet
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
© Travis Industries
Installation
Exhaust Restrictor
Position # 5 (closed)
Exhaust Restrictor
Removed (stock)
H1
(for qualified installers only)
Exhaust Restrictor
Position # 3
H2
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
4160429
This is considered a
vertical elbow
40' (12m) max
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
100-01406