Field-Supplied Disconnect
Switch Location
FIGURE 7 -
DISCONNECT/BLOWER ACCESS LOCATION
TABLE 28: UTILITIES ENTRY
HOLE
OPENING SIZE (DIA.)
A
1
7/8" KO
2" KO 1
B
C
1-5/8" KO
D
1-1/2" KO
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2" knockout ring.
28
Filter Access
Blower Motor Access
Dot Plugs
Mounting Bracket for
Disconnect Switch
(Field Supplied)
Disconnect Switch Location
and Motor Access Panel for
Unit with "Belt-Drive" Option
USED FOR
Side
2
Control Wiring
Bottom
Side
Power Wiring
Bottom
Gas Piping (Front)
Gas Piping (Bottom)
A,B
Wiring Entry
Control Box Access
(See Detail "B")
TABLE 29: MINIMUM CLEARANCES
LOCATION
Front
Rear
Left Side (Filter Access)
Right Side (Cond. Coil)
1
Below Unit
2
Above Unit
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.
254595-YTG-C-0308
CLEARANCE
24" (Cooling/Electric Heat)
32" (Gas Heat)
12" (Less Economizer)
36" (With Economizer or Fixed
Air/Motorized Damper)
24" (Less Economizer)
36" (With Economizer)
24"
0"
72" (For
Condenser Air Discharge)
Johnson Controls Unitary Products