Connecting The N2 Bus - Johnson Controls METASYS TEC1100 Series Technical Bulletin

Table of Contents

Advertisement

Table 10: TEC1103 Multistage Output Terminal Designations
Terminal
Function
W2
Energizes on call for second stage heat.
Y2
Energizes on call for second stage cooling.
W1
Energizes on call for first stage heat.
Y1
Energizes on call for first stage cooling.
G
Energizes fan on call for heating or cooling or by pressing the Fan button.
R
Independent switching voltage
24V
24 VAC from equipment transformer
24V(c)
24 VAC (common) from equipment transformer
LED 1, LED 2
Input connection that energizes LED 1 or LED 2 from remote status device to 24 VAC
CLK1, CLK2
Connections for remote clock/timer for alternate setpoints
RS2, RS1, RS+V
Connection for outdoor temperature sensor and/or indoor remote sensor option; refer to
instructions included with sensors.
N2+, N2-, REF
Metasys N2 Bus connections
If the transformer (T2) is to power all of the loads, the
yellow pin jumper must be inserted, which connects
R to 24 V. The jumper is located on the electronics
board above the relays. If a separate 24 V transformer
(T1) is to be used, it must be connected between
R and 24 V(c), and the jumper should not be
connected between R and 24 V.
Connecting the
N2 Bus
Jumper
W1
Y1
W2
Y2
Second
First Stage
Stage
Heat
Heat
Second
First Stage
Stage
Compressor
Compressor
Figure 8: TEC1103 Multistage Wiring Schematic
To connect the N2 Bus:
1. Observe the polarity when connecting the N2 Bus wires to the
TEC1100.
Note: Each TEC has self-terminating End-of-Line (EOL) resistors.
However, one EOL resistor is needed at the BAS (two are
preferred at opposite ends).
2. Continue this process for each TEC1100 using the daisy-chain wiring
method (Figure 9).
24 V
G
R
LED2
24 V(c)
Fan
Field Contact Switches
T1
T2
TEC1100 Series Thermostat Technical Bulletin
Metasys
CPN, FAC,
NCM
N2+
REF
N2-
Electronics
CLK2
RS+V
RS2
LED1
RS1
CLK1
Remote
Remote
Sensor
Clock/Timer
(if used)
(if used)
Msndiag
Thermostat
Equipment
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Metasys tec1103Metasys tec1102Metasys tec1101

Table of Contents