Table 5-10 Restore Factory Calibration - Honeywell UDC2500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

Input Calibration
ATTENTION
A restored factory calibration overwrites any previous field calibration done for the input and
may change the High and Low Range Limits.
Protect your field calibration from accidental overwrites by configuring the appropriate
LOCKOUT selection after calibration.
See the Section 3 - Configuration for specific instructions to set the lockout.
Step
Operation
Set LOCKOUT to
1
NONE
Enter INPUT 1
2
Setup Group
Scroll through
3
Functions
4
Return to Normal
Operation

Table 5-10 Restore Factory Calibration

Press
until you see:
SET UP
Upper Display = SET UP
Lower Display = LOCK
Until you see:
FUNCTION
Upper Display = one of the following:
NONE – all parameters are read/write
CAL – all parameters are read/write except Calibration
CONF – configuration parameters are Read Only; no writes
permitted
Lower Display = LOCK
Until NONE is in the upper display
or
until you see:
SET UP
Upper Display = SET UP
Lower Display = INPUT 1
until you see:
FUNCTION
Upper Display = the current selection
Lower Display = IN1TYP
to change the current selection to another selection
or
until the lower display rolls through the rest of the functions and
FUNCTION
returns to:
Upper Display = the new selection
Lower Display = INxTYP
until you change the input selection in the upper display back to the
or
proper selection. You will see:
Upper Display = Original Input Selection that matches your
type of sensor.
Lower Display = INxTYP
to return to Normal operating mode.
LOWER
DISPLAY
The factory calibration will be restored. If the problem is not
corrected, contact the Honeywell Technical Assistance Center.
1-800-423-9883 USA and Canada
UDC2500 Universal Digital Limit ControllerProduct Manual
Result
68