1. Screw
2. Panel Adaptor
2.
Install the supplied screws to secure the adapters to the panel.
Section 2.2

Connecting Power

The M2200 supports single or dual redundant AC and/or DC power supplies. The use of two power modules is
recommended to provide redundancy and load balancing.
The M2200 can be equipped with either a screw-type or pluggable terminal block, which provides power to both
power supplies. The screw-type terminal block is installed using Philips screws and compression plates, allowing
either bare wire connections or crimped terminal lugs. Use #6 size ring lugs for secure, reliable connections
under severe shock or vibration.
NOTE
• For maximum redundancy in a dual power supply configuration, use two independent power
sources.
• Use only #16 gage copper wiring when connecting terminal blocks.