TROUBLESHOOTING
FAN BLADE SETTING DIMENSIONS
Shown in Figure 7 is the correct fan blade setting
dimension for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in
the fan and/or motor area will require that the dimension
below be checked and blade adjusted in or out on the
motor shaft accordingly.
FIGURE 11
FAN BLADE SETTING DIMENSION
AIRFLOW
MIS-1724
TABLE 5
FAN BLADE DIMENSION
Model
W12AAA
R-410A
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of
refrigerant listed on the serial plate. AHRI capacity and
efficiency ratings were determined by testing with this
refrigerant charge quantity.
The following pressure tables show nominal pressures for
the units. Since many installation specific situations can
affect the pressure readings, this information should only
be used by certified technicians as a guide for evaluating
proper system performance. They shall not be used to
adjust charge. If charge is in doubt, reclaim, evacuate
and recharge the unit to the serial plate charge.
Manual 2100-618
Page
20 of 21
"A"
Dimension A
2.25"
TABLE 6
INDOOR BLOWER PERFORMANCE
E.S.P.
in
230V/115V-60Hz
H
O
Dry / Wet
2
.0
475 / 450
.1
425 / 400
.2
375 / 360
.3
315 / 300
.4
270 / 250
TABLE 7
RATED CFM AND ESP
RECOMMENDED AIRFLOW RANGE
Rated
Rated
Model
CFM
ESP
W12AAA
400
.10
TABLE 8
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
Model
W12AAAA00
A03
A05
W12AAAK00
K02
W12AAAD00
D03
Values shown are for units equipped with
STD 1" throwaway filters. Derate ESP
by .15 for 2" pleated filters.
W12AAA
240V-50Hz
Dry / Wet
395 / 375
355 / 330
310 / 300
260 / 250
225 / 210
Recommended
Airflow Range
475 - 300
ESP
.35
.35
.35
.35
.35
.35
.35