Thermistor - Navien NCB-24LSWE Service Manual

Condensing combi boiler
Hide thumbs Also See for NCB-24LSWE:
Table of Contents

Advertisement

4.9.3 Thermistor

Item
Function
Fault
Symptoms
Error codes
Diagnostics
Testing/inspection
information
Temp ( ℃ )
0-5
6-10
11-15
16-20
21-25
26-30
35-40
62 NCB Service Manual
Measure hot and cold water temperature at the boiler's space heating outlet and inlet
connections.
Inaccurate water temperatures from inside the boiler.
1. If a thermistor fails, an error code is displayed before the boiler operates.
2. If resistance values are outside the allowable range, there will be hot water temperature
fluctuations.
E047, E205, E218, E407, E421
1. Visual inspection: Check wire connections are secure and inspect for wire damage.
2. Test the resistance of the sensor. Before testing, shut down the boiler and allow it to cool.
Resistance range: Refer to the table below
Test for an open hot water temperature sensor (Test result: MΩ open)
Thermistor (kΩ)
[Space heating line]
23.4-19.1
18.3-15.5
14.8-12.6
12.1-10.7
10.3-8.5
8.2-7.0
6.8-4.9
Description
Thermistor (kΩ)
[DHW line]
27.5-22.2
21.2-18.0
17.3-14.7
14.2-12.1
11.6-10.0
9.6-8.3
8.0-6.9
Exhaust Limit Temperature
Sensor (kΩ)
162.3-125.9
119.8-98.5
93.8-77.6
74.0-61.6
58.8-49.2
47.1-39.5
37.9-32.0