Flue Installation - Buderus 500 - 24/S Installation And Maintenance Instructions Manual

Gas wall hung boiler condensing
Hide thumbs Also See for 500 - 24/S:
Table of Contents

Advertisement

1.7

Flue Installation

1.7.1
Siting the flue terminal
N
A
A
F
M
G
E
fig. 12 Flue terminal position
The flue must be installed in accordance with the recommen-
dations of BS. 5440-1:2000.
Pluming will occur at the terminal so terminal positions where
this could cause a nuisance should be avoided.
The air supply and the flue gas exhaust must meet the appli-
cable general regulations. Please consult the instructions
provided with the flue terminal kits prior to installation.
The boiler MUST be installed so that the terminal is exposed
to external air.
It is important that the position of the terminal allows the free
passage of air at all times.
Subject to modifications resulting from technical improvements!
Installation and maintenance instructions for Buderus 500 - 24/S • 08/2006
N
B,C
B,C
M
K
F
F
G
under carport
D
J
K
H, I
G
Terminal Position
O
A. Directly below, above or alongside
B. Below guttering, drain pipes or soil
C
C. Below eaves
D. Below balconies or a car port roof
E. From vertical drain pipes or soil
K
L
F. From internal or external corners
L
G. Above adjacent ground, roof or
K
H. From a surface facing the terminal
I.
G
J. From an opening in a car port (e.g.
K. Vertically from a terminal on the
L. Horizontally from a terminal on the
M. Adjacent to opening
F
N. Above intersection with roof
O. From a vertical structure on the roof
table 1
Installation
an opening window, air vent or
other ventilation opening
pipes
Not recommended!
pipes
balcony level
From a terminal facing a terminal
door or window) into dwelling.
Not recommended!
same wall
wall
Balanced flue terminal position
Buderus • http://www.buderus-domestic.co.uk
1
Minimum
Spacing
300 mm
200 mm
200 mm
200 mm
150 mm
300 mm
300 mm
600 mm
1200 mm
1200 mm
1500 mm
300 mm
300 mm
300 mm
500 mm
15