Link Adapter AL006-(P)E

5-5
Link Adapter AL006-(P)E
28
Use FC connecters for AGF cable. AGF connecters have fixed positions for re-
ception and transmission, so be careful to connect them correctly.
This Link Adapter can operate on either 100/200 VAC or 12-24 VAC/DC. The
repeater input terminals should be shorted across when not being used. For de-
tails on how to use the repeater input, see 2-6 Link Adapter Repeater Input . For
details on auxiliary power supplies, see 2-5 Backup Power Supply .